• 888-750-4777
  • This email address is being protected from spambots. You need JavaScript enabled to view it.
Welcome, Guest
Username: Password: Remember me
  • Page:
  • 1

TOPIC: Light switch in shower area

Light switch in shower area 12 years 4 months ago #45444

I know a light switch can not be inside the shower area. I did an inspection on a new construction and this switch was on the shower wall, Contractor says it's ok. The edge of the shower is directly below and slightly outside the switch. You do have to go around the corner for the shower area but one of the shower heads can spay on the switch. Any thoughts??
Attachments:

Please Log in to join the conversation.

Bent Nail Inspections
Serving Boise, Meridian, Eagle, Nampa, Caldwell and surrounding areas
Boise home inspector, boise home inspections, Meridian home inspector, Idaho Home Inspection, Nampa Home Inspector
Boise home Inspections   
www.bestboisehomeinspection.com/ ...

Re: Light switch in shower area 12 years 4 months ago #45445

The NEC states:  "Switches shall not be installed within wet locations in tub or shower spaces unless installed as part of a listed tub or shower assembly."

As long as the switch is even 1/16 of an inch outside the zone, it is fine.  The zone would be the footprint of the shower pan, straight up from the outside edge to the ceiling.

While allowed, due to the metal screws, I would recommend it be GFCI protected.

Please Log in to join the conversation.

There is nothing sweeter than the smell of fresh cut grass on a baseball infield, the click of a wooden bat and the taste of a hot dog at a warm sunny daytime double-header.
  • Page:
  • 1
Time to create page: 0.158 seconds
© 2004-2024 Home Inspector Pro Inc. All Rights Reserved.