• 888-750-4777
  • This email address is being protected from spambots. You need JavaScript enabled to view it.
Welcome, Guest
Username: Password: Remember me
  • Page:
  • 1

TOPIC: DOUBLE DOUBLE TAP ON MAIN BREAKER ?

DOUBLE DOUBLE TAP ON MAIN BREAKER ? 13 years 1 month ago #38488

Here is a nice big NO NO , LOL

Wonder how i should write it up, or how many ways i can write it up,

How would YOU all say it?
Attachments:

Please Log in to join the conversation.

Illinois- Tribuzio Home Inspection Services

www.thishomeinspector.com   (708) 453 8447

Home Inspection in Chicago land area and surrounding suburbs
Serving Chicago, Elmwood Park, Oak Park, Harwood Heights, Norridge, River Grove, Park Ridge and surrounding areas.

Re: DOUBLE DOUBLE TAP ON MAIN BREAKER ? 13 years 1 month ago #38490

  • Joe Tedesco
  • Joe Tedesco's Avatar
  • Offline
  • Senior Member
  • Senior Member
  • IAEI Certified Electrical Inspector since 1979
  • Posts: 58
  • Thank you received: 0
NEC Section 110.14(A): Terminals for more than one conductor and terminals used to connect aluminum shall be so identified.

NEC Article 100: Identified (as applied to equipment). Recognizable as suitable for the specific purpose, function, use, environment, application, and so forth, where described in a particular
Code requirement.

Informational Note: Some examples of ways to determine suitability of equipment for a specific purpose, environment, or application include investigations by a qualified testing laboratory (listing and labeling), an inspection agency, or other organizations concerned with product evaluation.

110.3(B) Installation and Use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling.

Please Log in to join the conversation.

Joe Tedesco, NEC® Consultant

Re: DOUBLE DOUBLE TAP ON MAIN BREAKER ? 13 years 1 month ago #38492

NEC Section 110.14(A): Terminals for more than one conductor and terminals used to connect aluminum shall be so identified.

NEC Article 100: Identified (as applied to equipment). Recognizable as suitable for the specific purpose, function, use, environment, application, and so forth, where described in a particular
Code requirement.

Informational Note: Some examples of ways to determine suitability of equipment for a specific purpose, environment, or application include investigations by a qualified testing laboratory (listing and labeling), an inspection agency, or other organizations concerned with product evaluation.

110.3(B) Installation and Use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling.



THANK YOU, THAT IS GOOD STUFF

Please Log in to join the conversation.

Illinois- Tribuzio Home Inspection Services

www.thishomeinspector.com   (708) 453 8447

Home Inspection in Chicago land area and surrounding suburbs
Serving Chicago, Elmwood Park, Oak Park, Harwood Heights, Norridge, River Grove, Park Ridge and surrounding areas.
  • Page:
  • 1
Time to create page: 0.179 seconds
© 2004-2024 Home Inspector Pro Inc. All Rights Reserved.