TOPIC: HVAC and breakers

Re: HVAC and breakers 12 years 8 months ago #43037

Agree with Jim. 30 AMP is preferred for this application (125% = 31.25 AMP's). If a 25 AMP was used, the breaker would trip often, due to the sartup spike of the electrical motor.

Please Log in to join the conversation.