Re: Sometimes A Separation Does Not Work 15 years 1 week ago #9745

Jay is correct above about the slip joint.
All too many times it is seen up here due to the frost action and settling in the spring.

Here is another example of one that has not broken yet. Similar 4/0 entrace feeder.



You might also note Jay that the 4/0 alluminum cable most likely does not enter the back of the main distribution panel and therefore I believe it needs to have a fused disconnect on the outside.
That is what happened in my picture. Was not legal then and not legal now.
Just caught my eye.  :)[/color]

Please Log in to join the conversation.

Cyr Home & Commercial Property Inspections
body text: Home and commercial property inspections across Maine, Kennebec county and all of Central Maine.
Keywords: Central Maine Home Inspectors, home inspector, commercial inspections
Meta tags:Serving all of Central Maine and surrounding areas
URL:...

Re: Sometimes A Separation Does Not Work 14 years 11 months ago #11011

What state is the house in ?

Please Log in to join the conversation.

Re: Sometimes A Separation Does Not Work 14 years 11 months ago #11013

New Hampshire, Why? :)

Please Log in to join the conversation.

Cyr Home & Commercial Property Inspections
body text: Home and commercial property inspections across Maine, Kennebec county and all of Central Maine.
Keywords: Central Maine Home Inspectors, home inspector, commercial inspections
Meta tags:Serving all of Central Maine and surrounding areas
URL:...

Re: Sometimes A Separation Does Not Work 14 years 11 months ago #11160

New Hampshire, Why? :)


Ive never seen that type of problem in Calif. 

Please Log in to join the conversation.

Re: Sometimes A Separation Does Not Work 14 years 11 months ago #11161

Marcel - sometimes around here the meters are on the back of townhouses and for some reason they aren't able to go into the back of the box, as you showed above.  In that instance they put another little one-breaker box beside the meter.  All it has in it is a main shut off.  There is another "main" in the panel box inside. 

I don't like the idea of having a box like that outside because I feel like anyone can get into it and turn off my juice.  That can be dangerous if someone has bad intentions.  Home invasions are a big deal around here and a bad guy can cut it off and burst into the house within seconds.  I would keep a big lock on the box, even if the electric company wanted access and would get upset seeing a lock. 

Please Log in to join the conversation.

Jay Markanich Real Estate Inspections, LLC
Based in Bristow, serving all of Northern Virginia
www.jaymarinspect.com
Northern Virginia Home Inspector
Festina Lente - Make Haste Slowly

Re: Sometimes A Separation Does Not Work 14 years 11 months ago #11175

Seems you guys need to move here were you don't have to worry about locking you external electrical panels! LOL

Please Log in to join the conversation.

HLC Home Inspections LLC
www.OklahomaHomeInspector.biz
We are a licensed inspector for the state of Oklahoma.?  Our focus is Oklahoma City, Moore, Mustang, Yukon, Tuttle, and many other areas surrounding OKC.
HLC-Home-Inspections-Oklahoma-City

HLC Home Inspections LLC...
Time to create page: 0.197 seconds
© 2004-2024 Home Inspector Pro Inc. All Rights Reserved.